We offer a wide range of products

On these pages, we show a selection of the thousands of products we can offer.
Feel free to contact us, and together, we will find exactly what you need for your construction.

FILTER

Ex ES 97 WH-11 -60°C

 

Ex position switch with safety function

  • Ex zone 1 and 21
  • Thermoplastic enclosure
  • Cold-resistant down to -60 °C
  • High degree of protection IP66 / IP67 / IP69
  • Design to EN 50047
  • Wiring compartment
  • Double insulated X
  • Actuator: Roller lever with collar WH

Notes
1 Ex”e” cable gland M20x1.5 included in delivery

Technical data

Applied standards

EN 60947-5-1, EN IEC 60079-0, EN 60079-1, EN IEC 60079-7, EN 60079-31, EN ISO 13849-1, EN ISO 14119

Enclosure

thermoplastic, glass-fibre reinforced, shockproof, self-extinguishing UL 94 V-0

Cover

thermoset, glass-fibre reinforced, shockproof, self-extinguishing UL 94 V-0

Sealing

silicone

Switch type

type 1

Coding level

no coding

Tightening torque

cover screws: 0.4 … 0.45 Nm

Degree of protection

IP66 to EN 60079-0 + IEC/EN 60529 (… -60 °C)
IP67 to EN 60079-0 + IEC/EN 60529 (… -20 °C)
IP67 / IP69 to IEC/EN 60529
IP69K to ISO 20653

B10d (10 % load)

2 million

TM

max. 20 years

Contact material

Silver, nickel-plated

Switching system

slow action, positive break NC contacts A

Switching elements

1 NC/1 NO contact, type Zb

Connection

screw connection terminals

Cable cross-section

min. 0.75 mm² (AWG 18), max. 1.5 mm² (AWG 16), incl. conductor ferrules

Cable entry

M20 x 1.5; screwing depth max. 9 mm; use only Ex approved and certified cable glands with min. degree of protection IP66 and suitable for the specified ambient temperature range

Clamping range

7 … 12 mm

Utilisation category

AC-15

Rated operating current Ie

max. 2 A or 4 A X

Rated operating voltage Ue

max. 500 VAC, max. 250 VAC for unequal potential

Degree of pollution

3

Mechanical life

> 1 million operations

Impact energy

max. 7 J

Temperature class

T6

Ambient temperature

–60 °C … +55 °C max. 4 A, +60 °C max. 2 A

Short-circuit protection

2 A / 4 A gG/gN fuse

Ex marking

L II 2G Ex db eb IIC T6 Gb,
L II 2D Ex tb IIIC T80 °C Db
IECEx Ex db eb IIC T6 Gb,
Ex tb IIIC T80 °C Db

Approvals

BVS 16 ATEX E 052
IECEx BVS 16.0052

Weight

102 g

Download

Mounting and wiring instructions – Ex 97

German, English, French, Italian, Portuguese

Data sheet – Ex ES 97 WH-11 -60°C

English