We offer a wide range of products

On these pages, we show a selection of the thousands of products we can offer.
Feel free to contact us, and together, we will find exactly what you need for your construction.

FILTER

GMI D5072D Intrinsically Safe Isolators

 

I.S. SIL2 Multifunction Temperature Converter

The Multifunction Temperature Converter D5072 accepts a low level dc signal from millivolt, thermocouple or 2-3-4 wire resistance/RTD or transmitting potentiometer sensor, located in Hazardous Area, and converts, with isolation, the signal to drive a Safe Area load, suitable for applications requiring SIL 2 level in safety related systems for high risk industries. Output signal can be direct or reverse. Modbus RTU RS-485 output is available on Bus connector. Cold junction compensation can be programmed as Internal: provided by an internal temperature sensor; Fixed: to a user-customizable temperature value; Remote: (only D5072D) connecting compensation RTD to one of the two ch. For D5072D module: duplicator function provides two independent outputs from one single input. Output function can be configured as: Adder, subtractor, low/high selector. Modules are provided with alarm function, which is available via photoMOS output.

FEATURES

  • SIL 2 / SC 3
  • Input from Zone 0/Div. 1
  • Installation in Zone 2/Div. 2
  • mV, TC, 2/3/4wire res./RTD or potentiometer input
  • Duplication/inversion/scaling/custom output
  • Selectable CJC: internal PT1000, external RTD or fixed
  • Fastest integration time: 50 ms
  • Burnout/internal/cjc/in sensor fault monitor
  • Alarm output with user-settable trip points
  • Modbus RTU RS-485 for monitor & configuration
  • Fully programmable operating parameters
  • High Accuracy, µP controlled A/D converter
  • Three port isolation, Input/Output/Supply
  • High Density, two channels per unit

CHANNELS

2

Technical data

Supply

Voltage 24 Vdc nom (18 to 30 Vdc), reverse polarity protected
Current Consumption 50 mA @ 24 Vdc with 20 mA out, typical.
Power Dissipation 1.0 W @ 24 Vdc with 20 mA out, typical.

Input

Type Millivolt, thermocouple, 2-3-4 wire RTD or 3 wire transmitting potentiometer. Refer to Instruction Manual for more details.
Integration time from 50 ms to 500 ms.
Input range ±500 mV (TC/mV), 0-4 kΩ (RTD/res), up to 10 kΩ (pot).
Thermocouple reference junction compensation programmable: internal Pt1000, fixed, external, or remote.

Output

Type Fully customizable 0/4 to 20 mA, on max. 300 Ω load source mode, current limited @ 24 mA. Refer to Instruction Manual for more details.
Transfer characteristic linear, direct or reverse on all input sensors.

Modbus interface

Type Modbus RTU RS-485 up to 115.2 kbps for monitor/configuration/control.

Input performance

Ref. Conditions 24 V supply, 250 Ω load, 23 ± 1 °C ambient temperature, slow integration mode, 3/4 wires configuration for RTD.
Calibration and linearity accuracy refer to Instruction Manual.
Temp. influence refer to Instruction Manual.
Ref. junction compensation accuracy ≤ ± 1 °C.

Output performance

Ref. Conditions 24 V supply, 250 Ω load, 23 ± 1 °C ambient temperature, slow integration mode, 3/4 wires configuration for RTD.
Calibration accuracy ≤ ± 10 µA
Linearity error ≤ ± 10 µA.
Temp. influence ≤ ± 2 µA/°C

Isolation

Test Voltage I.S. In/Out 2.5 kV; I.S. In/Supply 2.5 kV; I.S. In/I.S. In 500 V; Out/Supply 500 V; Out/Out 500 V.

Environmental conditions

Operating temperature temperature limits –40 to +70 °
Storage temperature temperature limits –45 to +80 °C.

Safety description

Equipment Associated apparatus and non-sparking electrical equipment.
Safety parameters Uo = 7.2 V, Io = 16 mA, Po = 27 mW, Ui = 12.8 V, Ci = 0 nF, Li = 0 nH at terminals 7-8-9, 10-11-12. Um = 250 Vrms or Vdc, -40 °C ≤ Ta ≤ 70 °C.

Mounting

Type DIN-Rail 35 mm, with or without Power Bus or on custom Term. Board.
Weight about 135 g
Connection by polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm² (13 AWG).
Dimensions Width 12.5 mm, Depth 123 mm, Height 120 mm.

Download

Datasheet Engelsk

Instructions manual, 5072

Instruction manual, D5000 – D5200 Series

G.M: International srl
G.M. International srl